| Line 316: | Line 316: | ||
| 1/6/12 || 2,470 || 471 || 2,590 || 0 || | | 1/6/12 || 2,470 || 471 || 2,590 || 0 || | ||
|- | |- | ||
| − | | 1/9/12 || 1,880 || 471 || || || | + | | 1/9/12 || 1,880 || 471 || 4,000 || 118 || |
|} | |} | ||
[[CLAS12_R1]] | [[CLAS12_R1]] | ||
Revision as of 23:13, 9 January 2012
Definitions
According to http://www.set3.com/standards.html
Originally Federal Standard 209E defined a class 10,000 clean room based on the particle counts given below. A class 10,000 clean room is currently defined as an ISO 7 clean room using the ISO standard 146441.
| Clas | maximum particles/m³ | ||||
| ISO-146441 | Federal Standard 209E | ≥0.3 µm | ≥0.5 µm | ≥1 µm | ≥5 µm |
|---|---|---|---|---|---|
| ISO-6 | 1,000 | 102,000 | 35,200 | 8,320 | 293 |
| ISO-7 | 10,000 | 352,000 | 83,200 | 2,930 | |
The clean room using the same above particle counts.
PCR specific
The Physics clean room is about 200
| Clas | Counts | ||||
| ISO-146441 | Federal Standard 209E | ≥0.3 µm | ≥0.5 µm | ≥1 µm | ≥5 µm |
|---|---|---|---|---|---|
| ISO-6 | 1,000 | 102,000 | 35,200 | 8,320 | 293 |
| ISO-7 | 10,000 | 70,400,000 | 83,200 | 2,930 | |
The average and SD are calculated by taking 5 minute measurements 5 times.
| Date | Counts | |||||
| ≥0.3 µm | ≥0.5 µm | ≥5 µm | ||||
|---|---|---|---|---|---|---|
| Goal | 79,400,000 | 16,640,000 | 586,000 | |||
| 8/11/11 | 6040 2532 | 914 491 | 33 34 | |||
Measurements in ISO mode
| Date | maximum particles/m³ | ||
| ≥0.5 µm | ≥5 µm | comment | |
| Goal | 352,000 | 2,930 | |
| 8/12/11 | 1,480 | 0 | |
| 8/16/11 | 12,100 | 1,700 | drapes have been open over weekend (painting floor) |
| 8/21/11 | 4,240 | 283 | |
Measurements in Single mode
Since 0.3 µm measurements are not a required measurement for Class 10,000, they are not included here.
August
| maximum particles/m³ | |||||
| Morning | Evening | ||||
| Date | ≥0.5 µm | ≥5 µm | ≥0.5 µm | ≥5 µm | Comments |
| Goal | 352,000 | 2,930 | 352,000 | 2,930 | |
| 8/21/11 | 6,990 | 353 | 25,000 | 3,880 | |
| 8/22/11 | 33,400 | 3,770 | 35,800 | 3,770 | |
| 8/23/11 | 9,300 | 353 | 38,100 | 3,770 | |
| 8/24/11 | 19,100 | 824 | 10,700 | 1,650 | |
- Turned on Clean room in the afternoon of 8/23/11
September
| maximum particles/m³ | |||||
| Morning | Evening | ||||
| Date | ≥0.5 µm | ≥5 µm | ≥0.5 µm | ≥5 µm | Comments |
| Goal | 352,000 | 2,930 | 352,000 | 2,930 | |
| 9/24/11 | 83,700 | 6,950 | 45,200 | 4,940 | |
| 9/25/11 | 23,100 | 2,120 | 45,200 | 4,360 | |
| 9/26/11 | 22,800 | 2,240 | 5,300 | 118 | |
| 9/27/11 | 1,060 | 235 | 25,800 | 2,710 | Adjustments to the chamber were being made within an hour of taking the evening particle count, this required the curtains being opened frequently |
| 9/28/11 | 1,180 | 0 | 7,060 | 471 | |
| 9/29/11 | 19,100 | 1,530 | 12,600 | 1,180 | |
| 9/30/11 | 10,100 | 824 | 4,470 | 471 | a concrete floor in the next room was cut before noon today (perhaps last night between 5pm and 10 pm) |
October
| maximum particles/m³ | |||||
| Morning | Evening | ||||
| Date | ≥0.5 µm | ≥5 µm | ≥0.5 µm | ≥5 µm | Comments |
| Goal | 352,000 | 2,930 | 352,000 | 2,930 | |
| 10/3/11 | 14,200 | 1,180 | 18,200 | 353 | Snap fasteners were being installed late this afternoon to close gaps in our clean room wall |
| 10/4/11 | 8,120 | 824 | 9,060 | 824 | |
| 10/5/11 | 2,240 | 353 | 1,410 | 0 | |
| 10/6/11 | 3,300 | 353 | 3,060 | 118 | |
| 10/7/11 | 824 | 118 | 6,710 | 235 | |
| 10/10/11 | 4,000 | 118 | 2,240 | 118 | |
| 10/11/11 | 1,650 | 235 | 2,830 | 118 | |
| 10/12/11 | 1,530 | 0 | 1,060 | 235 | |
| 10/13/11 | 2,240 | 353 | 5,060 | 118 | |
| 10/14/11 | 7,300 | 589 | 4,830 | 235 | |
| 10/17/11 | 4,830 | 235 | 15,300 | 471 | |
| 10/18/11 | 4,710 | 353 | 5,530 | 235 | |
| 10/19/11 | 8,710 | 353 | 4,120 | 235 | |
| 10/20/11 | 6,710 | 589 | 24,700 | 1,180 | They were cutting concrete in the adjacent room |
| 10/21/11 | 4,360 | 353 | 3,770 | 235 | |
| 10/22/11 | 3,180 | 235 | 5,410 | 118 | |
| 10/24/11 | 6,590 | 118 | 11,900 | 283 | The construction crew was digging outside and installing duct work in the adjacent rooms |
| 10/25/11 | 11,100 | 0 | 2,830 | 353 | |
| 10/26/11 | 3,060 | 0 | 7,180 | 353 | New pre-filters were installed last night |
| 10/27/11 | 942 | 0 | 5,410 | 353 | |
| 10/28/11 | 6,950 | 942 | 4,940 | 118 | |
| 10/31/11 | 3,060 | 0 | 4,360 | 0 | |
November
| maximum particles/m³ | |||||
| Morning | Evening | ||||
| Date | ≥0.5 µm | ≥5 µm | ≥0.5 µm | ≥5 µm | Comments |
| Goal | 352,000 | 2,930 | 352,000 | 2,930 | |
| 11/1/11 | 942 | 118 | 8,360 | 471 | |
| 11/2/11 | 1,880 | 118 | 1,180 | 118 | |
| 11/3/11 | 824 | 0 | 7,890 | 118 | |
| 11/4/11 | 0 | 0 | 5,890 | 118 | The morning values are not a typo |
| 11/5/11 | 12,900 | 1,060 | 2,000 | 0 | |
| 11/6/11 | 1,650 | 353 | 1,650 | 0 | |
| 11/7/11 | 4,240 | 0 | 8,830 | 235 | |
| 11/8/11 | 4,710 | 2,350 | 471 | 118 | The morning 5.0 µm counts were high, but still under class 10,000 specifications |
| 11/9/11 | 2,000 | 118 | 3,410 | 353 | |
| 11/10/11 | 1,650 | 0 | 13,800 | 1,060 | |
| 11/11/11 | 2,240 | 118 | 1,410 | 235 | |
| 11/14/11 | 1,410 | 0 | 2,240 | 118 | |
| 11/15/11 | 2,240 | 235 | 2,940 | 118 | |
| 11/16/11 | 1,060 | 118 | 2,000 | 235 | |
| 11/17/11 | 3,650 | 235 | 2,240 | 353 | |
| 11/18/11 | 589 | 0 | 2,120 | 118 | |
| 11/19/11 | 2,000 | 235 | |||
| 11/21/11 | 5,180 | 235 | 1,180 | 0 | |
| 11/22/11 | 4,120 | 353 | 6,830 | 235 | |
| 11/23/11 | 471 | 235 | 824 | 235 | |
| 11/28/11 | 235 | 0 | 1,650 | 0 | |
| 11/29/11 | 3,530 | 118 | 6,120 | 235 | |
| 11/30/11 | 1,530 | 0 | 4,830 | 235 | |
December
| maximum particles/m³ | |||||
| Morning | Evening | ||||
| Date | ≥0.5 µm | ≥5 µm | ≥0.5 µm | ≥5 µm | Comments |
| Goal | 352,000 | 2,930 | 352,000 | 2,930 | |
| 12/1/11 | 706 | 0 | 5,180 | 589 | |
| 12/2/11 | 1,180 | 118 | 1,180 | 118 | |
| 12/3/11 | 1,650 | 471 | |||
| 12/5/11 | 118 | 0 | 3,060 | 0 | |
| 12/6/11 | 2,470 | 235 | 5,180 | 589 | |
| 12/7/11 | 5,530 | 0 | 3,880 | 118 | |
| 12/8/11 | 2,240 | 0 | 10,500 | 942 | |
| 12/9/11 | 1,530 | 118 | 5,060 | 471 | |
| 12/12/11 | 9,530 | 471 | 4,120 | 353 | |
| 12/13/11 | 4,830 | 353 | 7,420 | 589 | |
| 12/14/11 | 1,770 | 118 | 13,100 | 824 | |
| 12/15/11 | 942 | 235 | The large roll up doors were installed earlier today. | ||
| 12/19/11 | 6,000 | 118 | 8,000 | 118 | |
| 12/20/11 | 26,700 | 1,180 | 2,590 | 0 | |
| 12/21/11 | 824 | 235 | 7,300 | 235 | |
| 12/22/11 | 2,470 | 353 | 4,360 | 235 | |
| 12/23/11 | 1,530 | 235 | 2,120 | 0 | |
January
| maximum particles/m³ | |||||
| Morning | Evening | ||||
| Date | ≥0.5 µm | ≥5 µm | ≥0.5 µm | ≥5 µm | Comments |
| Goal | 352,000 | 2,930 | 352,000 | 2,930 | |
| 1/3/12 | 1,290 | 118 | 4,470 | 589 | |
| 1/4/12 | 3,180 | 235 | 1,880 | 0 | |
| 1/5/12 | 2,240 | 235 | 3,530 | 235 | |
| 1/6/12 | 2,470 | 471 | 2,590 | 0 | |
| 1/9/12 | 1,880 | 471 | 4,000 | 118 | |