==Using local network card==
  
 
I decided to connect the ROC directly to the second 1 Gigabit ethernet card on the host in order to avoid setting up a firewall which makes our sys admin guys happy and allows CODA to work.
 
I decided to connect the ROC directly to the second 1 Gigabit ethernet card on the host in order to avoid setting up a firewall which makes our sys admin guys happy and allows CODA to work.
Line 47: Line 47:
 
  value = 0 = 0x0                                                                 
 
  value = 0 = 0x0                                                                 
  
 
+
==   Incorrect number Argument when downloading ==
2.)   Incorrect number Argument when downloading
 
  
 
  daLogMsg: Downloading configuration "SIS3610"
 
  daLogMsg: Downloading configuration "SIS3610"
Line 56: Line 55:
  
 
I had incorrectly connected my EB to my ER system
 
I had incorrectly connected my EB to my ER system
 +
 +
== ROC won't load VxWorks Kernel ==
 +
 +
If you have anout output to stdout from a .cshrc or .tcshrc login script then the ROC will have trouble loading the kernel.
 +
 +
I ran into this one when I deciced to "source CODA/setup" in order to define my CODA environmental variables when I log in.  The setup script did a "echo" and this caused the ROC to stop loading the kernel.  When I was watching via minicom all I saw was the word "Loading...".
  
 
[http://www.iac.isu.edu/mediawiki/index.php/Data_Acquisition Back to DAQ]
 
[http://www.iac.isu.edu/mediawiki/index.php/Data_Acquisition Back to DAQ]

Revision as of 22:11, 31 October 2007

Startup the processes

Start the following programs in the order below and in different xterm windows

1.)msqld 2.)minicom

cntrl-A P E to setup communication speeds
reboot to be sure ROC is alive

3.)et_start

you may need to delete the old memory file /tmp/et_sys_DAQ

4.)rcServer

5.) coda_eb -i -s DAQ -n eb1 -t CDEB

6.)coda_er -i -s DAQ -n LDS_ER -t ROC

7.) runcontrol

Select run configuration

Download configuration to ROC

Prestart

Run

debug FAQ

Using local network card

I decided to connect the ROC directly to the second 1 Gigabit ethernet card on the host in order to avoid setting up a firewall which makes our sys admin guys happy and allows CODA to work.

I had to tell the ROC to alias the new host names in the boot script


so in the file CODA/bootscripts/roc1.boot

I added the line

hostAdd "daq1","10.1.1.1"

You can do this on the roc as well and then on the ROC you can check the lookup tables using the command

-> hostShow                                                                     
hostname         inet address       aliases                                     
--------         ------------       -------                                     
localhost        127.0.0.1                                                      
roc1             10.1.1.2                                                       
localdaq         10.1.1.1          daq1                                         
value = 0 = 0x0                                                                 

Incorrect number Argument when downloading

daLogMsg: Downloading configuration "SIS3610"
Incorrect number of Arguments passed for ROL = 1
daLogMsg:  Incorrect number of Arguments passed for ROL = 1


I had incorrectly connected my EB to my ER system

ROC won't load VxWorks Kernel

If you have anout output to stdout from a .cshrc or .tcshrc login script then the ROC will have trouble loading the kernel.

I ran into this one when I deciced to "source CODA/setup" in order to define my CODA environmental variables when I log in. The setup script did a "echo" and this caused the ROC to stop loading the kernel. When I was watching via minicom all I saw was the word "Loading...".

Back to DAQ