File:Humidity 7-18-12.PNG

From New IAC Wiki
Revision as of 23:35, 18 July 2012 by Lewimar3 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Humidity_7-18-12.PNG(630 × 447 pixels, file size: 43 KB, MIME type: image/png)

Cleanroom temperatures were above 72 ° F this morning. The increase in temperature appears to coincide with a dramatic decrease in humidity from above 50% to below 30%. (Pocatello is experiencing higher temperatures with little humidity.) The temperature setpoint on the HVAC was lowered to 68 °. Stringing operations were haulted briefly until temperatures decreased and stabilized around 71 °. At 10:00am the temperature setpoint was lowered to 67 °. Temperatures have decreased and stabilized between 69 ° and 70 °. (Screen shots of the temperature and humidity graphs were uploaded to the wiki.)

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current20:13, 18 July 2012Thumbnail for version as of 20:13, 18 July 2012630 × 447 (43 KB)Lewimar3 (talk | contribs)

There are no pages that use this file.